SEE Cooler S is a patented extremely energy efficient Tele & Datacom cooler to be connected directly to the coolant.
Low internal power consumption and high cooling effect compared to conventional technology. Equipped with EC fans.
Built in redundancy and a minimum of moving parts make it optimal for high cooling effects W/m².
SEE Cooler S is designed to work in a free cooling solution at coolant temperatures between +5 and 20°C.
The SEE Cooler S has an integrated control unit as well as capabilities of centralized monitoring and control.
Technical Data | S-1 | S-2 | S-3 | ||
Total capacity 1) | kW | 11,9 | 23,8 | 35,7 | |
Sensible capacity 1) | kW | 11,1 | 22,3 | 33,4 | |
COP1) | 136 | 136 | 136 | ||
Air flow | m3/s | 0,64 | 1,28 | 1,92 | |
Coolant | l/s | 0,3 | 0,6 | 0,9 | |
Pressure drop | kPa | 35 | 35 | 35 | |
Power input (P1) | kW | 0,08 | 0,16 | 0,24 | |
Rated current | A | 1x0,35 | 2x0,35 | 3x0,35 | |
Fans | # | 1 | 2 | 3 | |
Dry weight | kg | 158 | 239 | 324 | |
Sound level 2) | dBA | 44 | 47 | 49 |
1) Coolant inlet = 10ºC, Air inlet = 27,5ºC, Room conditions: 24ºC, 50% RH
2) At 5 meter distance from unit in typical environment
Cooling Capacity | S-1 | S-2 | S-3 |
Coolant tempin | Sens kW / Tot kW | Sens kW / Tot kW | Sens kW / Tot kW |
7,0ºC | 12,6 / 15,3 | 25,1 / 30,5 | 37,6 / 45,8 |
10,0ºC | 11,1 / 11,9 | 22,3 / 23,8 | 33,4 / 35,7 |
12,5ºC | 9,7 / 9,7 | 19,5 / 19,5 | 29,2 / 29,2 |
15,0ºC | 8,1 / 8,1 | 16,2 / 16,2 | 24,4 24,4 |
17,5ºC | 6,5 / 6,5 | 13,0 /13,0 | 19,5 / 19,5 |
20,0ºC | 5,0 / 5,0 | 10,1 / 10,1 | 15,2 /15,2 |
Air inlet = 27,5ºC, Room conditions : 24ºC, 50% RH